Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 651

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

V500/V520 Bar Code Reader Protocol
Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses.
2. Ladder Interface Settings
YES: User settings are required for the 3rd and 4th operands of PMCR(260).
NO:
Send word allocation:
Receive word allocation:
3. Sequences No. 361 and No. 364 (Continuous Data Read with Interrupt) are not supported by the
CS1W-SCU@@(-V1) and CJ1W-SCU@@(-V1) Serial Communications Units. A protocol syntax error
will occur if an attempt is made to execute either sequence with the Serial Communications Unit.
Connections
The connections for using the V500/V520 Bar Code Reader Protocol are shown below.
V500 Connections
622
Set the constant 0000 for the 3rd operand (S).
Set the constant 0000 for the 4th operand (D).
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
RS-232C port
Serial Communications Unit/Board:
D-sub 9 pin female
Signal
Pin No.
Name
1
FG
2
SD
3
RD
RTS
4
5
CTS
7
DSR
8
DTR
SG
9
100 VAC
V500-C11
ID Controller
V500-C11:
D-sub 9 pin female
Pin No.
Appendix M
V520-R12#
Reader
V509-W040
Reader Cable
Signal
Name
1
FG
2
SD
3
RD
RTS
4
CTS
5
DSR
7
8
DTR
SG
9