Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 582

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

E5 @ J Temperature Controller Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
Read Input Shift Value (Sequence No. 210 (Hex 00D2))
Reads the input shift value and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
+0
Number of receive data words
+1
Proportional band
+2
Integral time
+3
Derivative time
~
+91
Proportional band
Integral time
+92
+93
Derivative time
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
1st unit
Proportional band (4 digits BCD)
+2
1st unit
Integral time (4 digits BCD)
+3
1st unit
Derivative time (4 digits BCD)
+4
2nd unit
Proportional band (4 digits BCD)
+93
31th unit
(max.)
Derivative time (4 digits BCD)
+0
Number of send data words
+1
(Undefined)
Unit No.
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+0
Number of receive data words
+1
Input shift value
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
Input shift value (4 digits BCD)
1st unit
~
31th unit (max.)
Number of units × 3 + 1
0000 to 9999
When the left digit is –1, A is set and when it
is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it
is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it
is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it
is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it
is –, F is set.
0002 (fixed)
00 to 31
0002
0000 to 9999
When the left digit is –1, A is set and when it
is –, F is set.
Appendix J
Data
Data
Data
553

Hide quick links:

Advertisement

Table of Contents
loading