Auxiliary Area and CIO Area Allocations
8-3-2
CIO Area Allocations
Serial Communications
Boards (CS Series Only)
Serial Communications
Units (CS/CJ Series)
Words in the CIO Area are allocated for a Status Area, which contains status
and error information for the Serial Communications Board or Unit. These
allocations are described in this section.
Words CIO 1900 to CIO 1999 in the Inner Board Area are used for a Status
Area. Only the words shown in the following table are used for the Status Area
with 1:N NT Links.
Inner Board CIO Area
CIO 1900 to CIO 1999
Words
CIO 1901 to CIO 1904
CIO 1905 to CIO 1914
CIO 1915 to CIO 1924
CIO 1925 to CIO 1999
Words CIO 1500 to CIO 1899 in the CPU Bus Unit Area in the CIO Area are
allocated according to the unit number setting. Each Unit is allocated 25
words. Only the words shown in the following table are used for the Status
Area with 1:N NT Links.
CPU Bus Unit Area
CIO 1500 to CIO 1899
n = CIO 1500 + 25 × unit number
Unit No.
Words
Unit No. 0
CIO 1500 to CIO 1524
Unit No. 1
CIO 1525 to CIO 1549
Unit No. 2
CIO 1550 to CIO 1574
Unit No. 3
CIO 1575 to CIO 1599
Unit No. 4
CIO 1600 to CIO 1624
Unit No. 5
CIO 1625 to CIO 1649
Unit No. 6
CIO 1650 to CIO 1674
Unit No. 7
CIO 1675 to CIO 1694
Unit No. 8
CIO 1700 to CIO 1724
Unit No. 9
CIO 1725 to CIO 1749
Unit No. A
CIO 1750 to CIO 1774
Unit No. B
CIO 1775 to CIO 1799
Unit No. C
CIO 1800 to CIO 1824
Unit No. D
CIO 1825 to CIO 1849
Unit No. E
CIO 1850 to CIO 1874
Unit No. F
CIO 1875 to CIO 1899
Section 8-3
Usage
Board status
Port 1 status
Port 2 status
Reserved
n + 1 to n + 4: Unit status
n + 5 to n + 14: Port 1 status
n + 15 to n + 24: Port 2 status
269