Serial Gateway Overview

6-1
Serial Gateway Overview
6-1-1

Overview

6-1-2

Operating Conditions

6-1-3

Features

Unifying to FINS Networks for CompoWay/F-compatible OMRON Components
196
FINS messages (commands) that are received are automatically converted
into the corresponding protocol and then sent via serial communications. The
responses are also automatically converted. FINS messages can be con-
verted into the following protocols.
• CompoWay/F
• Modbus-RTU
• Modbus-ASCII
• Host Link FINS (FINS commands enclosed in Host Link header and ter-
minator)
Note Serial Communications Boards/Units can receive FINS commands
via a FINS network (including Host Link FINS) or via the CPU bus.
The Serial Gateway is enabled under the following conditions.
• When Serial Gateway mode is set as the serial communications mode.
• When protocol macro mode is set as the serial communications mode,
and the Serial Gateway Prohibit Switch is OFF. (The serial gateway is also
enabled during execution of PMCR(260) instructions.)
FINS message (via network or CPU bus)
FINS header
CompoWay/F command
2803
FINS header
Modbus-RTU command
2804
FINS header
2805
Modbus-ASCII command
User-
FINS header
User-specified data
specified
The Serial Gateway is enabled under the following conditions.
• In Serial Gateway mode
• In protocol macro mode with the Serial Gateway Prohibit Switch turned OFF
Pre-Ver. 1.2 Units
To access an OMRON CompoWay/F-compatible component (e.g., Tempera-
ture Controller or Digital Panel Meter) by sending user-specified CompoWay/F
commands from the PLC, the standard system protocol, CompoWay/F Mas-
ter, must be executed. This operation is performed by executing the
PMCR(260) instruction in the ladder program of the CPU Unit on the same
PLC using the Board/Unit's protocol macro function.
This protocol macro function, however, does not enable access through the
network. (When execution of a user-specified CompoWay/F command is not
required, a CJ1W-CIF21 Simple Communications Unit can be used to share
specified data without using communications instructions.)
RS-232C or RS-422A/485
CompoWay/F command
Serial
Modbus-RTU command
Communications
Board/Unit
Modbus-ASCII command
Host Link header
Section 6-1
User-specified
Terminator
FINS command