E5 @ K Digital Controller Write Protocol
Write Level 1 Parameter 2 (Sequence No. 067 (Hex 0043))
Writes parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hystere-
sis (cooling), control period (heating), and control period (cooling)) to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
494
+0
Number of send data words
Number of units
+1
(Undefined)
+2
+3
Cooling coefficient
+4
Dead band
+5
Manual reset value
+6
Hysteresis (heating)
+7
Hysteresis (cooling)
Control period (heating)
+8
Control period (cooling)
+9
~
(Undefined)
+58
+59
Cooling coefficient
+60
Dead band
+61
Manual reset value
+62
Hysteresis (heating)
+63
Hysteresis (cooling)
+64
Control period (heating)
Control period (cooling)
+65
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Number of units (4 digits Hex)
+2
1st unit
Unit No. (2 digits BCD)
+3
1st unit
Cooling coefficient (4 digits BCD)
+4
1st unit
Dead band (4 digits BCD)
+5
1st unit
Manual reset value (4 digits BCD)
+6
1st unit
Hysteresis (heating)
(4 digits BCD)
+7
1st unit
Hysteresis (cooling)
(4 digits BCD)
+8
1st unit
Control period (heating)
(4 digits BCD)
+9
1st unit
Control period (cooling)
(4 digits BCD)
+65
8th unit
(max.)
Control period (cooling)
(4 digits BCD)
Unit No.
1st unit
~
Unit No.
8th unit (max.)
Number of units × 8 + 2
0001 to 0008
00 to 31
0001 to 9999
0000 to 9999
0000 to 1000
0001 to 9999
0001 to 9999
0001 to 0099
0001 to 0099
0001 to 0099
Appendix G
Data