Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 517

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

E5 @ K Digital Controller Write Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Manual Reset Value (Sequence No. 055 (Hex 0037))
Writes the manual reset value.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Hysteresis (Sequence No. 056 (Hex 0038))
Writes the hysteresis for heating and for cooling.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Control Period (Sequence No. 057 (Hex 0039))
Writes the control period for heating and for cooling.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
488
+0
Number of send data words
+1
(Undefined)
Manual reset value
+2
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
Manual reset value (4 digits BCD)
Number of send data words
+0
+1
(Undefined)
+2
Hysteresis (heating)
Hysteresis (cooling)
+3
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
Hysteresis (heating)
(4 digits BCD)
+3
Hysteresis (cooling)
(4 digits BCD)
+0
Number of send data words
+1
(Undefined)
+2
Control period (heating)
+3
Control period (cooling)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
Unit No.
0003 (fixed)
00 to 31
0000 to 1000
Unit No.
0004 (fixed)
00 to 31
0001 to 9999
0001 to 9999
Unit No.
0004 (fixed)
00 to 31
Appendix G
Data
Data
Data

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents