E5ZE Temperature Controller Write Protocol
Write Alarm Temperature (Setting Unit 1) (Sequence No. 156
(Hex 009C))
Writes the alarm temperatures using a setting unit of 1 (4 digits)
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
+0
Number of send data words
+1
(Undefined)
+2
Alarm 1 set value
+3
(Undefined)
+4
Alarm 2 set value
+5
(Undefined)
~
+30
Alarm 1 set value
(Undefined)
+31
Alarm 2 set value
+32
(Undefined)
+33
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Alarm 1 set value
(4 digits BCD)
+3
Not used
+4
Channel 0
Alarm 2 set value
(4 digits BCD)
+5
Not used
+32
Channel 7
Alarm 2 set value
(4 digits BCD)
+33
Not used
Unit No.
Channel 0
~
Channel 7
0022 (0034 decimal) (fixed)
00 to 0F
0000 to 9999
0000 to 9999
•
•
•
0000 to 9999
Appendix I
Data
529