Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 585

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

E5 @ J Temperature Controller Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
General-purpose Write (Sequence No. 216 (Hex 00D8))
Writes the parameter specified by setting a header code.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
General-purpose Read (Sequence No. 217 (Hex 00D9))
Reads the parameter specified by setting a header
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
556
+0
Number of receive data words
+1
(Undefined)
+2
(Undefined)
Alarm 1 type
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
Status (2 digits Hex)
+2
Alarm 1 type (1 digit Hex)
Alarm 2 type (1 digit Hex)
Input type (1 digit BCD)
+0
Number of send data words
+1
(Undefined)
+2
Header code (ASC)
+3
(Undefined)
Data code
+4
Send data
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
Header code (two ASCII characters)
+3
Data code (2 digits BCD)
+4
Write data (4 digits BCD)
+0
Number of send data words
+1
(Undefined)
Unit No.
+2
Header code (ASC)
+3
(Undefined)
Data code
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
Header code (two ASCII characters)
+3
Data code (2 digits BCD)
Status
Input type
Alarm 2 type
0003
00 to 99
0 to 9
0 to 9
0 to 9
Unit No.
0005 (fixed)
00 to 31
Header codes that can be set
MB, WS, W%, WW, WB, WN, WV
01 to 02
0000 to 9999
0004 (fixed)
00 to 31
Header codes that can be set
RS, R%, RW, RB, RN, RV, RO
01 to 02
Appendix J
Data
Data
Data

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents