Auxiliary Area and CIO Area Allocations
Status Area Descriptions
Name
Address
Error log
Board:
data error
CIO 190101
Unit:
n + 1 bit 01
Protocol
Board:
data error
CIO 190100
Unit:
n + 1 bit 00
Board only:
A42409
Setup error
Board:
CIO 190601 (port 1)
CIO 191601 (port 2)
Unit:
n + 6 bit 01 (port 1)
n + 16 bit 01 (port 2)
Board only:
A42408 (not avail-
able for Unit)
Port operat-
Board:
ing
CIO 190600 (port 1)
CIO 191600 (port 2)
Unit:
n + 6 bit 00 (port 1)
n + 16 bit 00 (port 2)
Remote Unit
Board:
receive
CIO 190710 (port 1)
busy/receive
CIO 191710 (port 2)
wait
Unit:
n + 7 bit 10 (port 1)
n + 17 bit 10 (port 2)
Meaning
If a write to EEPROM fails for the error log, it
is assumed the EEPROM is beyond its use-
ful life and this flag is turned ON. With a
Serial Communications Unit, the ERC indica-
tor will also light. Although this has no effect
on communications and other functions,
replace the Board or Unit promptly for ease
of maintenance.
This flag is turned ON if an error is detected
in the protocol data SUM check when the
power is turned ON. With a Serial Communi-
cations Board, the ERR/ALM indicator on the
CPU Unit will also flash and the RDY indica-
tor will flash at 1-second intervals. A42409
(Board only) of the Auxiliary Area will also
turn ON.
With a Serial Communications Unit, the RDY
and ERC indicator will flash.
This error may occur if the communications
connector becomes disconnected or the
PLC power is turned OFF during protocol
data transfer. Use the CX-Protocol to trans-
fer of the protocol data again.
This flag is turned ON if a Setup error occurs
in the allocated DM Area, After changing the
Setup, turn ON the power again, restart the
Board/Unit, restart the port, or execute the
STUP(237) instruction.
ON when the port can operate correctly.
OFF when protocol macro data is being
transferred.
This flag indicates the receive status of a
remote Unit during SEND when Xon/Xoff
flow control or RS/CS flow control is set in
the transmission control parameters. When
Xon/Xoff flow control is set, the reception
buffer is cleared when the sequence starts,
so the status area is set to remote Unit
receive wait (0).
1: Remote Unit receive busy
(Reception is disabled because the
reception buffer is full.)
0: Remote Unit receive wait (Reception is
enabled.)
Section 5-3
Timing
Initialize
ON
Startup
At error
Startup
(see note)
Startup
At error
When pro-
(see note)
tocol data
has been
success-
fully trans-
ferred
Startup
At error
Startup
(see note)
(see note)
Startup
At error
After pro-
(see note)
tocol data
has been
transferred
Startup
When sta-
After busy
(see note)
tus is read
status has
been
released
OFF
167