E5ZE Temperature Controller Read Protocol
Read Control Period (Sequence No. 105 (Hex 0069))
Reads the control periods and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
510
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
Channel 0
Constant P (4 digits BCD)
+2
Channel 0
Constant I (4 digits BCD)
+3
Channel 0
Constant D (4 digits BCD)
+22
Channel 7
Constant P (4 digits BCD)
+23
Channel 7
Constant I (4 digits BCD)
+24
Channel 7
Constant D (4 digits BCD)
+0
Number of send data words
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+0
Number of receive data words
+1
Control period
+2
Cooling control period
+3
Control period
+4
Cooling control period
~
+15
Control period
+16
Cooling control period
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
Channel 0
Control period (4 digits BCD)
+2
Channel 0
Cooling control period
(4 digits BCD)
+15
Channel 7
Control period (4 digits BCD)
+16
Channel 7
Cooling control period
(4 digits BCD)
0019 (0025 decimal)
0000 to 9999
0000 to 3999
0000 to 3999
•
•
•
0000 to 9999
0000 to 3999
0000 to 3999
Unit No.
0002 (fixed)
00 to 0F
Channel 0
Channel 1
~
Channel 7
0011 (0017 decimal)
0001 to 0099
0001 to 0099
•
•
•
0001 to 0099
0001 to 0099
Appendix H
Data
Data
Data