Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 557

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

E5ZE Temperature Controller Write Protocol
Write Output Mode (Sequence No. 154 (Hex 009A))
Writes the output mode (normal/reverse).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Alarm Mode (Sequence No. 155 (Hex 009B))
Writes the alarm modes for alarm 1 and alarm 2.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
528
Number of send data words
+0
+1
(Undefined)
+2
(Undefined)
Write code
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Write code (2 digits Hex)
+0
Number of send data words
+1
(Undefined)
+2
(Undefined)
Alarm 1 set code
+3
(Undefined)
Alarm 2 set code
+4
(Undefined)
Alarm 1 set code
+5
(Undefined)
Alarm 2 set code
~
+16
(Undefined)
Alarm 1 set code
(Undefined)
alarm 2 set code
+17
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Alarm 1 set code (2 digits Hex)
+3
Channel 0
Alarm 2 set code (2 digits Hex)
+4
Channel 1
Alarm 1 set code (2 digits Hex)
+5
Channel 1
Alarm 2 set code (2 digits Hex)
+16
Channel 7
Alarm 1 set code (2 digits Hex)
+17
Channel 7
Alarm 2 set code (2 digits Hex)
Unit No.
0003 (fixed)
00 to 0F
00 to FF
Unit No.
Channel 0
Channel 1
~
Channel 7
0012 (0018 decimal) (fixed)
00 to 0F
00 to 0C
00 to 0C
00 to 0C
00 to 0C
00 to 0C
00 to 0C
Appendix I
Data
Data

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents