E5ZE Temperature Controller Write Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Output Value Change Rate Limit (Sequence No. 167 (Hex
00A7))
Writes the output value change rate limits that restrict the rates of change in the control value output.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
536
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Output value lower limit
(4 digits BCD)
+3
Channel 0
Output value upper limit
(4 digits BCD)
+4
Channel 0
Cooling output value lower limit
(4 digits BCD)
+5
Channel 0
Cooling output value upper limit
(4 digits BCD)
+32
Channel 7
Cooling output value lower limit
(4 digits BCD)
+33
Channel 7
Cooling output value upper limit
(4 digits BCD)
+0
Number of send data words
+1
(Undefined)
+2
Output change rate limit
+3
Output change rate limit
+4
Output change rate limit
+5
Output change rate limit
+6
Output change rate limit
+7
Output change rate limit
Output change rate limit
+8
+9
Output change rate limit
0022 (0034 decimal) (fixed)
00 to 0F
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
•
•
•
0000 to 1000
0000 to 1000
Unit No.
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7