I/O Memory Allocations
TXDU(256)/RXDU(255) Instruction Bits for No-protocol Mode
88
Unit
Port 1 Settings Change Bit
Unit No. A
A63001
Unit No. B
A63101
Unit No. C
A63201
Unit No. D
A63301
Unit No. E
A63401
Unit No. F
A63501
Restart Bit
A Restart Bit can be turned ON and then OFF to restart the Serial Communi-
cations Board without turning OFF the PLC power supply.
Unit
A50100
Unit No. 0 Restart Bit
A50101
Unit No. 1 Restart Bit
A50102
Unit No. 2 Restart Bit
A50103
Unit No. 3 Restart Bit
A50104
Unit No. 4 Restart Bit
A50105
Unit No. 5 Restart Bit
A50106
Unit No. 6 Restart Bit
A50107
Unit No. 7 Restart Bit
A50108
Unit No. 8 Restart Bit
A50109
Unit No. 9 Restart Bit
A50110
Unit No. A Restart Bit
A50111
Unit No. B Restart Bit
A50112
Unit No. C Restart Bit
A50113
Unit No. D Restart Bit
A50114
Unit No. E Restart Bit
A50115
Unit No. F Restart Bit
Word
Bit
A202
00 to 07 Network Communications Enabled Flag
Turns ON when execution of network communications instruc-
tions (SEND(090), RECV(098), CMND(490), and PMCR(260))
including TXDU(256) and RXDU(255) instructions is enabled.
A203 to
00 to 15 Network Communications Completion Code
A210
Stores the completion code for network communications
instructions (SEND(090), RECV(098), CMND(490), and
PMCR(260)) including TXDU(256) and RXDU(255) instructions
that have been executed.
A219
00 to 07 Communication Port Error Flags
Turn ON if an error occurs during execution of network commu-
nications instructions (SEND(090), RECV(098), CMND(490),
and PMCR(260)) including TXDU(256) and RXDU(255) instruc-
tions.
Port 2 Settings Change Bit
A63002
A63102
A63202
A63302
A63402
A63502
Function
Contents
Section 2-3