Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 490

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Device Memory Batch Read as Bit Data (T/C Device Type)
(Sequence No. 815 (Hex 032F)) (Command Code: JR)
This sequence reads the bit (PV) data for the number of device points starting from the specified device
address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station
number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the
specified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Number of send data words
+0
First word of
send data
+1
Station No.
Device type
+2
+3
Device No.
+4
+5
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits hex)
+1
Station No.
(2 digits hex)
Device type (4 digits hex)
+2
Device No. (5 digits hex)
+3
+4
(Undefined)
+5
(Undefined)
Number of receive data words
+0
Receive data
storage words
Station No.
+1
+2
Read data
Offset
Contents (data format)
Number of receive data words
+0
+1
Station No.
(2 digits hex)
+2
Read data (4 digits hex)
PLC No.
(Undefined)
Number of device
words/bits
Always 0006 hex (6 decimal)
PLC No.
Station No.: 00 to FF hex
(2 digits hex)
PLC No.: 00 to FF hex
Set the device type (1 character) in
ASCII.
Set the first read address of the device
to read.
Device words/
Set the number of device words/bits to
bits
read.
(2 digits hex)
PLC No.
0003 to 00FA hex (3 to 250 decimal)
PLC No.
Station No.: 00 to FF hex
(2 digits hex)
PLC No.: 00 to FF hex
Stores the number read data converted
into hexadecimal.
Appendix E
Data
Data
461

Hide quick links: