Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 754

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

V600/V620 ID Controller Protocol
Polling Auto-write Command Processing Cancel (Sequence
No. 545 (Hex 0221))
This sequence cancels polling auto-write processing
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 544 (Polling Auto-read Command Processing
Cancel)
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 544 (Polling Auto-read Command Process-
ing Cancel)
General-purpose Command (Sequence No. 546 (Hex 0222))
This sequence transmits arbitrary data and stores receive data to the receive data words. The characters "@",
FCS (terminator) are not required in the send data words and receive data words. These characters will be
automatically added for transmission and automatically removed before saving data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Storage Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
+0
Number of send data words
+1
Send data byte length
Send data
+2
~
+249
Send data
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Send data byte length
(4 digits Hex)
+2 to
Send data (ASCII)
+249
+0
Number of receive data words
Receive data
+1
~
+249
Receive data
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1 to
Receive data
+249
(ASCII)
~
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
The number of bytes in the send data except
for @, the FCS, and the terminator.
Input send data up to 496 characters (max.)
in ASCII
~
0002 to 00FA (2 to 250 decimal)
Receive data is stored in ASCII.
Up to 498 characters (max.)
Appendix P
Data
Data
725

Hide quick links: