Troubleshooting
Board/Unit
Serial com-
status
munications
mode
The con-
The serial
verted
communica-
command
tions mode is
could be
set to Serial
sent to the
Gateway or
remote
protocol
device but
macro mode.
a normal
response is
not
received
from the
remote
device.
322
Error conditions
Indicator
FINS end
display
code sent to
FINS trans-
mission
source
Either the
0205 hex
SD@/RD@
(response
and COM@
timeout), etc.
indicators all
flash.
The SD@
0205 hex
and COM@
(response
indicators
timeout), etc.
flash, but a
response is
not always
returned.
The RD@/
SD@, and
COM@ indi-
cators all
flash, but a
response is
not always
returned.
Cause
Words allo-
cated in CIO
Area
Bit 05 of CIO
The response
word n+8/
from the remote
n+18 (Serial
device is too fast
Gateway Send
and the data
Start Time-
received by the
out/ Response
Board/Unit has
Timeout) is
been discarded.
ON.
Bit 02, 03, 04,
A hardware error
or 15 of CIO
has occurred in
word n+8/
the reception cir-
n+18 (transfer
cuit of the Board/
error, overrun
Unit.
error, framing
error, or parity
error) is ON.
A transmission
error has occurred
due to noise.
Section 11-3
Remedy
Delay the response from
the remote device.
Conduct a loopback test
in serial communications
mode to check the trans-
mission lines. If an error
occurs during the test,
replace the Board or
Unit.
Use shielded twisted-
pair cables.
Lay power lines sepa-
rately using ducts.
Increase the number of
resends at the FINS
transmission source.
Perform communications
retry as required.