K3T @ Intelligent Signal Processor Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
Read Set Value HH with Bank (Continuous Units)
(Sequence No. 323 (Hex 0143))
This sequence reads set value HH of a bank not in use for continuous units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
`
Receive Data Word Allocation (4th Operand of PMCR(260))
The word allocation is similar to sequence No. 322 (Read Set Value with Bank (by Unit Number)).
Read Set Value H with Bank (Continuous Units)
(Sequence No. 324 (Hex 0144))
This sequence reads set value H of a bank not in use for continuous units. The word allocation is identical to
that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
612
+0
Number of receive data words
+1
Set value
+2
(Undefined)
~
+63
Set value
+64
(Undefined)
Offset
Contents (data format)
+0
Number of receive data
words (4 digits Hex)
+1 to +2 Set value
(5 digits BCD)
+63 to
Set value
+64
(5 digits BCD)
+0
Number of send data words
+1
Number of units
+2
(Undefined)
~
(Undefined)
+33
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Number of units (4 digits Hex)
+2
Bank No. (2 digits BCD)
+ 33
Bank No. (2 digits BCD)
Set value
~
Set value
0003 to 0041 (3 to 65 decimal)
00000 to 99999
Negative sign: F (5th digit in BCD)
Example 12345
+1
2345
+2
0001
Same as above
Bank No.
~
Bank No.
0003 to 0022 (3 to 34 decimal)
0001 to 0020 (1 to 32 decimal)
01 to 04
Same as above
Appendix L
Data
Example –1234
+1
1234
+2
000F
Data