Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 414

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

CompoWay/F Master Protocol
Variable Area Fill
(Sequence No. 613 (Hex 0265))
This sequence writes the same data from the address of the specified variable type to the specified node num-
ber.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Variable Area Broadcast Send
(Sequence No. 614 (Hex 0266))
This sequence writes the same data from the address of the specified variable using a broadcast address.
Send Data Word Allocation (3rd Operand of PMCR(260))
Number of send data words
+0
First word of
send data
+1
(Undefined)
+2
Variable type
+3
First write address
Number of elements
+4
+5
Number of bytes to write
Offset
Contents (data format)
+0
Number of send data words
+1
(Undefined)
Node No.
(2 digits BCD)
+2
Variable type
(2 digits hex)
+3
First write address (6 digits BCD)
+4
Number of elements
(4 digits BCD)
+5
Number of bytes to write
(4 digits hex)
+0
Receive data
Number of receive data words
storage words
+1
Response code
Offset
Contents (data format)
+0
Number of receive data words
+1
Response code (4 digits hex)
Number of send data words
+0
(Undefined)
First word of
+1
send data
+2
Variable type
+3
First write address
Number of elements
+4
+5
Node No.
Always 0006 hex (6 decimal)
00 to 99
Set the area type (2 digits) and the first read
word (6 digits). The leftmost byte of the first write
address specifies the address and the rightmost
byte specifies the bit location. Set the rightmost
byte to 00 when bit access is not required.
Set the number of elements to write.
Set the write data.
Always 0002 hex (2 decimal)
The CompoWay/F command response code
is stored in hexadecimal code.
Write data