Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 481

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Device Memory Batch Read as Bit Data (All Device Types Except T/C)
(Sequence No. 806 (Hex 0326)) (Command Code: BR)
This sequence reads the bit data for the number of device points starting from the specified device address for
the specified device type (except T, C) in the Mitsubishi Computer Link Module with the specified station num-
ber (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the spec-
ified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
452
+0
Number of send data words
First word of
send data
+1
Station No.
+2
(Undefined)
+3
Device No.
+4
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits hex)
Station No.
+1
(2 digits hex)
(Undefined)
+2
+3
Device No. (4 digits hex)
+4
(Undefined)
Number of receive data words
+0
Receive data
storage words
+1
Station No.
+2
Read data
Offset
Contents (data format)
+0
Number of receive data words
Station No.
+1
(2 digits hex)
+2
Read data (4 digits hex)
PLC No.
Device type
Number of device
words/bits
Always 0005 hex (5 decimal)
PLC No.
Station No.: 00 to FF hex
(2 digits hex)
PLC No.: 00 to FF hex
Device type
Set the device type (1 character) in
(2 digits hex)
ASCII.
Set the first read address of the device
to read.
Device words/
Set the number of device words/bits to
bits
read.
(2 digits hex)
PLC No.
0003 to 00FA hex (3 to 250 decimal)
PLC No.
Station No.: 00 to FF hex
(2 digits hex)
PLC No.: 00 to FF hex
Stores the number read data converted
into hexadecimal.
Appendix E
Data
Data

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents