Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 537

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

E5ZE Temperature Controller Read Protocol
Read Set Point, Process Value, and Output Value
(Sequence No. 103 (Hex 0067))
Reads the set points, process values, and output values and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
508
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
Channel 0
Output value (4 digits BCD)
+2
Channel 0
Cooling output value (4 digits BCD)
+3
Channel 1
Output value (4 digits BCD)
+4
Channel 1
Cooling output value (4 digits BCD)
+15
Channel 7
Output value (4 digits BCD)
+16
Channel 7
Cooling output value (4 digits BCD)
+0
Number of send data words
(Undefined)
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+0
Number of receive data words
Set point (rightmost 4 digits)
+1
+2
Set point (leftmost 1 digit)
+3
Process value (rightmost 4 digits)
+4
Process value (leftmost 1 digit)
Output value
+5
~
+36
Set point (rightmost 4 digits)
+37
Set point (leftmost 1 digit)
+38
Process value (rightmost 4 digits)
+39
Process value (leftmost 1 digit)
+40
Output value
0011 (0017 decimal)
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
Unit No.
0002 (fixed)
00 to 0F
~
Appendix H
Data
Data
Channel 0
Channel 7