Setup Area Contents - Omron SYSMAC CS1W-SCB41-V1 Operation Manual

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Setup Area Allocations (Modbus-RTU Slave Mode)
9-2-2

Setup Area Contents

Words
Board
(CS Series only)
Port 1
Port 2
D32000
D32010
m
D32001
D32011
m + 1
D32002 to
D32012 to
m + 2 to
D32005
D32015
m + 5
D32006
D32016
m + 6
D32007 to
D32017 to
m + 7 to
D32009
D32019
m + 9
D32020
D32030
m + 20
D32021
D32031
m + 21
D32022 to
D32032 to
m + 22 to
D32029
D32039
m + 29
Port Settings
Bit
Unit
(CS/CJ Series)
Port 1
Port 2
m + 10
15
12 to 14
08 to 11
05 to 02
01
00
m + 11
04 to 15
00 to 03
m + 12 to
15
m + 15
14 to 00
m + 16
15 to 08
07 to 00
m + 17 to
15 to 08
m + 19
07 to 00
m + 30
15 to 08
07 to 00
m + 31
15 to 08
07 to 00
m + 32 to
15 to 08
m + 39
07 to 00
The setting for the port settings determine if the default settings or user set-
tings will be used for port 1 and port 2. Be sure to use the same settings as
the communications port on the host computer connected via the Modbus-
RTU Slave System.
If the default port settings are specified, then the setting of bits 00 and 01 and
the baud rate in D32001 will be ignored.
The default settings used are as follows: Baud rate: 19,200 bps, start bits:
1 bit, data length: 8 bits, parity: even, and stop bits: 1 bit.
If user port settings are specified, set bits 00 and 01 and set the baud rate in
D32001.
Setting contents
Port settings
0: Defaults; 1: User settings
Reserved
Serial communications mode
A hex: Modbus-RTU slave
Reserved
Parity
0: Yes; 1: No
Parity
0: Even; 1: Odd
Reserved
Baud rate (bps)
0: Default (19,200); 3: 1,200; 4: 2,400; 5: 4,800; 6: 9,600;
7: 19,200; 8: 38,400; 9: 57,600; A: 115,200
Reserved.
Reserved.
Modbus Slave Address
01 to F7 hex (1 to 247)
Reserved.
Reserved.
Reserved.
Reserved.
Coils Allocation Area
00 hex: CIO Area
B0 hex: CIO Area, B1 hex: Work Area, B2 hex: Holding Area,
B3 hex: Auxiliary Area
Input Registers Allocation Area
00 hex: CIO Area
B0 hex: CIO Area, B1 hex: Work Area, B2 hex: Holding Area,
B3 hex: Auxiliary Area
Holding Registers Allocation Area
00 hex: DM Area
82 hex: DM Area
50 to 5C hex: EM Area, bank 0 to C
A0 to AC hex: EM Area, bank 0 to C
98 hex: Current bank of EM Area
Reserved.
Reserved.
Section 9-2
m = D30000 + 100 × Unit No.
277