Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 502

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

E5 @ K Digital Controller Read Protocol
Read SP Ramp Time Unit and Set Value (Sequence No. 011 (Hex
000B))
Reads the SP ramp time unit and SP ramp set value and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
Read LBA Detection Time (Sequence No. 012 (Hex 000C))
Reads the LBA (loop break alarm) detection time and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
+0
Number of send data words
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+0
Number of receive data words
+1
SP ramp time unit
+2
SP ramp set value
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
SP ramp time unit (4 digits BCD)
+2
SP ramp set value (4 digits BCD)
Number of send data words
+0
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
Number of receive data words
+0
LBA detection time
+1
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
LBA detection time (4 digits BCD)
Unit No.
0002 (fixed)
00 to 31
0003
0000: s, 0001: h
0000 to 9999
Unit No.
0002 (fixed)
00 to 31
0002
0000 to 9999