E5ZE Temperature Controller Read Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
Read Input Shift Value (Sequence No. 113 (Hex 0071))
Reads the input shift values and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
Read Manual Reset Value (Sequence No. 114 (Hex 0072))
Reads the manual reset value and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
+0
Number of receive data words
+1
Set code
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
Set code (4 digits BCD)
Number of send data words
+0
(Undefined)
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+0
Number of receive data words
+1
Input shift value
Input shift value
+2
~
Input shift value
+8
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
Channel 0
Input shift value (4 digits BCD)
+2
Channel 1
Input shift value (4 digits BCD)
+8
Channel 7
Input shift value (4 digits BCD)
Number of send data words
+0
(Undefined)
Unit No.
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
0002
0000: unit of 1
0001: unit of 0.1
Unit No.
0002 (fixed)
00 to 0F
Channel 0
Channel 1
~
Channel 7
0009
0000 to 0999
F indicates a negative number.
0000 to 0999
F indicates a negative number.
0000 to 0999
F indicates a negative number.
0002 (fixed)
00 to 0F
Appendix H
Data
Data
Data
Data
515