E5ZE Temperature Controller Write Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Cooling Coefficient (Sequence No. 173 (Hex 00AD))
Writes the cooling coefficients for the cooling proportional bands for heating/cooling control.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
540
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Dead band/overlap band
(4 digits BCD)
+3
Channel 1
Dead band/overlap band
(4 digits BCD)
+4
Channel 2
Dead band/overlap band
(4 digits BCD)
+8
Channel 6
Dead band/overlap band
(4 digits BCD)
+9
Channel 7
Dead band/overlap band
(4 digits BCD)
Number of send data words
+0
+1
(Undefined)
+2
Cooling coefficient
+3
Cooling coefficient
+4
Cooling coefficient
Cooling coefficient
+5
+6
Cooling coefficient
+7
Cooling coefficient
+8
Cooling coefficient
Cooling coefficient
+9
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Cooling coefficient (4 digits BCD)
+3
Channel 1
Cooling coefficient (4 digits BCD)
+4
Channel 2
Cooling coefficient (4 digits BCD)
+8
Channel 6
Cooling coefficient (4 digits BCD)
+9
Channel 7
Cooling coefficient (4 digits BCD)
000A (0010 decimal) (fixed)
00 to 0F
0000 to 0999
0000 to 0999
0000 to 0999
0000 to 0999
0000 to 0999
Unit No.
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
000A (0010 decimal) (fixed)
00 to 0F
0000 to 0100
0000 to 0100
0000 to 0100
0000 to 0100
0000 to 0100
Appendix I
Data
Data