Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 670

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

3Z4L Laser Micrometer Protocol
3Z4L Clear (Sequence No. 400 (Hex 0190))
This sequence resets errors, data, analog output, and decision result, and puts the Laser Micrometer into
standby.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Memory Switch Set (Sequence No. 401 (Hex 0191))
This sequence sets memory switches and the area for the work position LED.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
mm Unit Set (Sequence No. 402 (Hex 0192))
This sequence sets the display unit to mm.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON.
E Unit Set (Sequence No. 403 (Hex 0193))
This sequence sets the display unit to E.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
+0
Number of send data words
+1
W
X
Y
(Undefined)
+2
Offset
Contents
(data format)
+0
Number of send data
words (4 digits Hex)
+1
w (1 digit BCD)
x (1 digit BCD)
y (1 digit BCD)
z (1 digit BCD)
+2
v (1 digit BCD)
Z
V
Data
3000-series
0003 (fixed)
Using buzzer sound: 0 to 3
Automatic latch release time:
0 to 9
Using print timer, the setting
for simultaneous measure-
ment: 0 to 3 (high-speed), 0
to 1 (other)
Display of the comma for 1/
1000s digit, number of
display digits: 0 to 5 (high-
speed), 0 to 3 (other)
Measurement interval 4: 0 to
6
Appendix N
4000-series
0003 (fixed)
Number of digits for extin-
guishing indicator: 0 to 2
I/O IF RUN Input: 0 or 1
Display of Err–0: 0 or 1
Averaging method: 0 to 2
(high-speed), 0 (other)
Use of comma: 0 or 1
641

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents