Mitsubishi Q00JCPU User Manual page 624

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

APPENDICES
Number
Name
Meaning
Diagnostic
Diagnosis error
SD0
errors
code
SD1
Clock time for
Clock time for
diagnosis error
diagnosis error
SD2
occurrence
occurrence
SD3
Error
Error information
SD4
information
category code
categories
App
Appendix 2 Special Register List
- 29
(1) Diagnostic Information
TableApp.18 Special register
• Error codes for errors found by diagnosis are stored as BIN data.
• Contents identical to latest fault history information.
• Year (last two digits) and month that SD0 data was updated is stored as
BCD 2-digit code.
b15
to
b8
b7
Year (0 to 99) Month (1 to 12)
• The day and hour that SD0 was updated is stored as BCD 2-digit code.
b15
to
b8
b7
Day (1 to 31) Hour (0 to 23)
• The minute and second that SD0 data was updated is stored as BCD 2-
digit code.
b15
to
b8
b7
Minutes (0 to 59) Seconds (0 to 59)
Category codes which help indicate what type of information is being
stored in the common information areas (SD5 through SD15) and the
individual information areas (SD16 through SD26) are stored here.
The category code for judging the the error information type is stored.
b15
to
Individual information
category codes
• The common information category codes store the following codes:
0 : No error
1: Unit/module No./ PLC No./Base No.
2: File name/Drive name
3: Time (value set)
4: Program error location
5: System switching cause (for Q4ARCPU, Redundant CPU only)
6: Reason(s) for tracking capacity excess error (specific to Redundant
CPU)
7: Power supply No. (specific to Redundant CPU)
8: Tracking transmission data classification (specific to Redundant CPU)
*: For a multiple CPU system that consists of the Basic model QCPU,
High Performance model QCPU and Process CPU, the module
number or CPU number is stored depending on the error that
occurred.
(Refer to the corresponding error code for which number has been
stored.)
PLC No. 1: 1, PLC No. 2: 2, PLC No. 3: 3, PLC No. 4: 4
• The individual information category codes store the following codes:
0: No error
1: (Vacancy)
2: File name/Drive name
3: Time (value actually measured)
4: Program error location
5: Parameter number
6: Annunciator number
7: Check instruction malfunction number (This does not apply to the
Basic model QCPU)
8: Reason(s) for system switching failure (specific to Redundant CPU)
Explanation
(Example) October, 1995
to
b0
H9510
(Example) 10 a.m. on 25th
to
b0
H2510
(Example) 35 min. 48 sec.
to
b0
H3548
b8
b7
to
b0
Common information
category codes
*
Corres-
ponding
Set by
Corresponding
ACPU
(When set)
D9
D9008
S (Error)
format
change
S (Error)
New
S (Error)
New
CPU
Rem

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents