Mitsubishi Q00JCPU User Manual page 343

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

6
FUNCTIONS
Basic
Note6.41
(6) Error check selection
Note42Çñ
Basic
In the case of the Basic model QCPU, a memory card access error, memory card operation error
or external power supply OFF cannot be set.
Note6.41
(b) Errors that can be set to continue/stop the operation
The following errors can be set to "continue/stop" the operation when they have
occurred.
1) Errors that can be set to continue/stop the operation in PLC RAS setting
of PLC parameter dialog box
• Computation error
• Expanded Command error
• Fuse blown
• I/O module comparison error
• Intelligent module program execution error
• Memory card access error
• Memory card operation error
• External power supply OFF
For example, when the I/O module verification error is set to "continues", the
calculations are continued in the I/O address before the error occurred.
2) Error can be set to continue/stop the operation in detail setting of I/O
assignment setting of PLC parameter dialog box
• Intelligent function module error
The following error checking can be set to "yes/no" at the "PLC RAS" tab screen in the
"(PLC) Parameter" dialog box.
(All parameter defaults are set at "Yes".)
(a)
Battery check
(b)
Fuse blown check
(c)
I/O module comparison