(3) Setting the constant scanning time
The constant scanning time is set at the "PLC RAS" tab screen in the "(PLC)
Parameter" dialog box.
The constant scanning time can be set within the following range.
When executing constant scanning, set the constant scanning time.
When not executing a constant scanning, leave the constant scanning time blank.
• For Basic model QCPU
1 to 2000ms (set in 1ms unit)
• For High Performance model QCPU, Process CPU or Redundant CPU
0.5 to 2000ms (set in 0.5ms unit)
Diagram 6.2 When constant scanning is set to 10ms