Mitsubishi Q00JCPU User Manual page 266

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

6
FUNCTIONS
6
6.6 Remote Operation
- 25
6.6.2 Remote PAUSE
POINT
Setting of only the PAUSE contact is not allowed.
When setting the PAUSE contact, also set the RUN contact.
(b) Method with GX Developer, Serial Communication Module etc.
The remote PAUSE operation can be performed from the GX Developer or by
using serial communication module.
Operate GX Developer by choosing [Online]
When executing remote PAUSE from an external device using MC protocol, use
the MC protocol command.
Q Corresponding MELSEC Communication Protocol Reference Manual
• When the END processing is performed for the scan where the remote
PAUSE command was accepted, the PAUSE status contact (SM204) is
turned on.
When the scan after the PAUSE status contact is turned on is executed to the
END process, it enters the PAUSE status and stops the calculations.
• When the remote RUN command is received, the sequence program
calculations are performed again from step 0.
0
OFF
Remote PAUSE
command
OFF
Remote RUN
command
OFF
SM204
RUN
RUN/PAUSE
status
END
0
END
ON
ON
ON when
PAUSE
condition met
Diagram 6.17 PAUSE Time Chart with GX Developer
[Remote operation].
0
ON
PAUSE
PAUSE status
0
END

Hide quick links: