Mitsubishi Q00JCPU User Manual page 151

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

4
I/O NUMBER ASSIGNMENT
(2) Precautions for the number of mounted modules
Mount modules within the range of the allowed number of slots.
Even if the total number of slots for a main base unit and extension base unit is
greater than the number of available slots (for example, six 12-slot base units are
used), no error will occur when modules are mounted in slots whose number is within
a valid range.
An error ("SP. UNIT LAY ERR.") will occur if any module is mounted after the slot
exceeding the number of available slots.
Power supply
module
Main base unit
Q312B
CPU
0
1
2
3
CPU module
Extension base unit
Q612B
12
13
14
15
16
17
18
Q612B
24
25
26
27
28
29
30
Q612B
36
37
38
39
40
41
42
Q612B
48
49
50
51
52
53
54
Q612B
60
61
62
63
Modules can be
Modules cannot be installed.
installed.
(Installing modules will result in error.)
Diagram 4.3 Configuration example for High Performance model QCPU
4.2 Relationship between No. of Extension Stages and No. of Slots
4
5
6
7
8
9
10
11
19
20
21
22
23
Extension 1
Extension 2
31
32
33
34
35
43
44
45
46
47
Extension 3
Extension 4
55
56
57
58
59
Extension 5
Slot number
When the GOT has been bus-
connected, one slot of extension
base 1 is used.
Also one GOT occupies 16 I/O
points.
When using the GOT, consider
the number of slots and the
number of I/O points.
Refer to the GOT Manual for
details of busconnecting the GOT.
1
2
3
4
5
6
7
8
4
- 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents