Mitsubishi Q00JCPU User Manual page 376

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

6
FUNCTIONS
6
6.21 LED Display
- 135
6.21.2 Priority setting
POINT
1. When leaving the LED turned off at the error described above, set the factor
No. setting area (each 4 bits), which stores the factor No. corresponding to
SD207 to 209 to "0".
[Example]
To leave the ERR. LED off when a fuse shutoff error is detected, set the factor
No. setting area to "0" where the error No. is "2".
0
Because the factor No. "2" is not set, the ERR. LED remains off even if
the fuse shutoff is detected. In this case, even if another error with the
factor No. "2" (I/O module verify error or intelligent function module verify
error) is detected, the ERR. LED remains off.
2. If 0 is set to the factor No. setting area (setting that does not turn on the LED),
SM0 (diagnostics error flag) is turned ON, SM1 (self diagnostics error flag) is
turned ON, and the error code is stored into SD0 (diagnostics error register).
SD209
SD208
0
A
9
8
7
6
Diagram 6.79 Factor No. stored in SD 207 to 209.
SD207
5
4
3
0
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents