6
FUNCTIONS
POINT
1 . If a step between the AND/OR blocks is specified as a monitor condition,
monitor data is sampled when the status previous to execution of the
specified step is specified by the LD instruction. The monitor timing depends
on the step specified as a monitor condition. The following shows examples of
monitoring when the Step 2 is ON (Step No. [ 2] = <ON>).
• When the Step 2 is connected by the AND instruction:
In Diagram 6.28, the monitor execution condition is established when
both "X0" and "X1" are ON.
X0
X1
0
Diagram 6.28 When the Step2 is connected by the AND instruction
• When the Step 2 is connected between the AND/ON blocks:
In Diagram 6.29, the monitor execution condition is established when
"X1" is ON. Whether "X0" is ON or OFF, it does not affect the monitor
execution condition.
X0
X1
0
X3
Diagram 6.29 When the Step 2 is connected between the AND/ON blocks
• If the beginning of a ladder block not at Step 0 is specified in Step No. as
a detailed condition, monitor data is collected when the execution status
of the instruction immediately before execution becomes the specified
status. If (Step No. [ 2] = <ON>) is specified in the following ladder,
monitor data is collected when OUT Y10 turns ON.
X0
0
X1
2
Diagram 6.30 When the beginning of a ladder block not at Step 0 is specified in Step No.
2 . Be sure to set the condition of the step set as step No.0 to "Always".
Ladder mode
Step 2
X2
Y20
Ladder mode
Step 2
X2
Y20
Ladder mode
Y10
Y11
6.11 Monitor Function
6.11.1 Monitor condition setting
List mode
0 LD
X0
1 AND X1
2 AND X2
3 OUT Y20
List mode
0 LD
X0
1 LD
X1
2 AND X2
3 OR
X3
4 ANB
5 OUT Y20
List mode
0 LD
X0
1 OUT Y10
2 LD
X1
3 OUT Y11
6