PARAMETERS
(6) Device
Item
Parameter No.
Device points
2000
Latch (1) start/end
2001
Latch (2) start/end
2002
Local device start/end
2003
Set the number of used points, latch range and local device range for each device.
Table8.17 Device list
Description
Set the number of used device
H
points according to the system.
Set the latch range (first device
number/last device number) in
which clear is enabled by the
H
RESET/L.CLR switch or remote
latch clear operation.
Set the latch range (first device
number/last device number) in
which clear is disabled by the
H
RESET/L.CLR switch or remote
latch clear operation.
Set the device range (first device
number/last device number)
H
used as a local device.
8.1.2 High Performance model QCPU, Process CPU, Redundant CPU
Diagram 8.17 Device
Setting range
X
Y
M :8k points
X (8k points), Y (8k points), S (8k
L
points), SB (2k points) and SW
B
(2k points) are fixed.
F
Can be set within the range of
SB :2k points
total 29k words, including the
V
above number of points (3.7k
S
words).
T
• 1 device: Max. 32k points
ST :0k points
• Total of bit devices: 64k points
C
D
W :8k points
SW :2k points
Set only one range to each of the
B, F, V, T, ST, C, D and W
No setting
devices.
Set only one range to each of the
L, B, F, V, T, ST, C, D and W
No setting
devices.
Set only one range to each of the
No setting
M, V, T, ST, C and D devices.
8.1 PLC Parameters
Default value
Reference
:8k points
:8k points
:8k points
:8k points
:2k points
Section 9.1
:2k points
Section 9.2
:8k points
:2k points
:1k points
:12k points
Section 3.7
Section 6.3
Section 3.7
Section 6.3
Section 9.13.1
8
- 21
1
2
3
4
5
6
7
8