Mitsubishi Q00JCPU User Manual page 345

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

6
FUNCTIONS
Diagnosics
Intelligent function
1
module error *
Hardware
failure
Control bus error
Momentary stop
occurred
Redundant base unit
power supply voltage
drop
Redundant power
supply module fault
Battery low
I/O module verification
*1
Base assignment error
Intelligent function
module allocation error
Handling
error
Intelligent program
execution error *1
Intelligent function
module version error
No parameter
Boot error
Table6.29 Self-dianostics list (Continued)
Error message
Diagnostics timing
• When the CPU
module is powered
on/reset
• When FROM/TO
instruction is executed
SP.UNIT DOWN
• When intelligent
function module
dedicated instruction
is executed
• When END instruction
is executed
• When the CPU
module is powered on
• When END instruction
is executed
• When FROM/TO
CONTROL-BUS
instruction is executed
ERR.
• When intelligent
function module
dedicated instruction
is executed
• Always
AC/DC DOWN
• Always
SINGLE PS. DOWN
• Always
SINGLE PS.
• Always
ERROR
• Always
BATTERY ERROR
• (Default ... checked)
• When the END
instruction is executed
UNIT VERIFY ERR.
• (Default... checked)
• When the CPU
BASE LAY ERROR
module is powered
on/reset
• When the CPU
module is powered
SP.UNIT LAY ERR.
on/reset
• When switched from
STOP to RUN
• When the FROM/TO
SP.UNIT ERROR
instruction is executed
• When the CPU
SP.UNIT VER.ERR
module is powered
on/reset
• When the CPU
MISSING PARA.
module is powered
on/reset
• When the CPU
BOOT ERROR
module is powered
on/reset
* 1 : Can be changed to "Continue" in the parameter setting of GX Developer.
* 2 : Can be changed to "not checked" in the parameter setting of GX Developer. Not checked when
SM251 is ON.
* 3 : Can be changed to "not checked" in the parameter setting of GX Developer.
LED status
CPU module
status
RUN
STOP/
OFF/ON
Continue
STOP
OFF
Continue
ON
Continue
ON
Continue
ON
Continue
ON
*3
STOP
/
OFF
/ON
Continue
*2
STOP
OFF
STOP
OFF
STOP
/
OFF
/ON
Continue
STOP
OFF
STOP
OFF
STOP
OFF
: Self-diagnostics is performed
6.17 Self-diagnostics Function
CPU module
ERR.
1)
2)
3)
4)
Flicker/ON
Flicker
OFF
ON
ON
BAT.ALM
LED ON
Flicker
/ON
Flicker
Flicker
Flicker
/ON
Flicker
Flicker
Flicker
: Self-diagnostics is not performed
(Continued on next page)
6
- 104
1
2
3
4
5
6
7
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents