Mitsubishi Q00JCPU User Manual page 297

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

6
FUNCTIONS
(2) Explanation of specifications
Basic
Note6.14
Note14
The enforced ON registration and enforced OFF registration cannot be executed for
Basic
Basic model QCPU by selecting [Online]
Note6.14
registration/cancellation] (
model QCPU by conducting device test with GX Developer.
(a) CPU module status for which enforced ON/OFF can be executed
Enforced ON/OFF can be performed regardless of the CPU module is RUN/STOP
status. However, enforced ON/OFF is only allowed for input during stop errors.
The output is only performed to device Y.
(b) Devices that can be registered
The number of devices as many as CPU module's I/O device points can be
registered.
Note6.14
(
CHAPTER 2 )
(c) Target I/O for enforced ON/OFF
The input and output eligible for enforced ON/OFF are shown below.
• I/O (X/Y) of modules on main base unit.
• I/O (X/Y) of CPU module to which LX/LY of MELSECNET/H module is
refreshed
• I/O (X/Y) of CPU module to which RX/RY of CC-Link to be refreshed
When enforced ON/OFF is performed for devices outside the above refresh
ranges (ex: empty slots) only the High Performance model QCPU device memory
is set at ON/OFF, and this is not output externally.
Note14
[Debug]
[Forced input output
(3) in this section). This operation can be executed for Basic
6.11 Monitor Function
6.11.3 Enforced ON/OFF of external I/O
1
2
3
4
5
6
7
8
6
- 56