Mitsubishi Q00JCPU User Manual page 594

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

11
PROCEDURE FOR WRITING PROGRAM TO CPU
MODULE
11
11.2 High Performance Model QCPU, Process CPU, Redundant CPU
- 15
11.2.4 Procedure for writing multiple programs
2)
Connect the personal computer, which is
installed with GX Developer, to the CPU
module.
Set the RUN/STOP switch to STOP and
the RESET/L.CLR switch to the neutral
position, and power ON the PLC (the
ERR. LED turns on).
Choose [Online]
[Format PLC memory]
on GX Deveoper, and format the program
memory.
Choose [Online]
[Write to PLC] on GX
Developer, select "Program
memory/device memory", and write the
parameters, created program, etc.
Power the PLC OFF and then ON, or
reset the CPU module.
Set the RUN/STOP switch to the RUN
position to place the PLC in the RUN
status.
Is the ERR.
NO
LED of the CPU
module on
(flickering)?
YES
Choose [Diagnosis]
on GX Developer or perform PLC
diagnosis to check the error factor, and
remove the error factor.
NO
Is boot run
executed?
YES
End
To Section 11.2.5
* 2 : Refer to the following manual for the procedure when the Redundant CPU is used.
QnPRHCPU User's Manual (Redundant System)
* 3 : When storing the file register and device initial value data into the standard RAM or memory card
(except the Flash card), also format the standard RAM or memory card.
* 4 : Write each data to the following memory.
•Program ..... Program memory
•Parameter ..... Memory set as the parameter-valid drive with the DIP switches
•Device initial value ..... Memory specified in the PLC file setting of the PLC parameter dialog box
Diagram 11.6 Flowchart for writing multiple programs
2
3
4
............
2
[System monitor]
Write to PLC screen
Troubleshooting of QCPU User's Manual
(Hardware Design, Maintenance and
Inspection)