Mitsubishi Q00JCPU User Manual page 599

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

APPENDICES
(2) System information
Number
Name
SM202
LED OFF command
OFF
SM203
STOP contact
STOP status
SM204
PAUSE contact
PAUSE status
SM205
STEP-RUN contact
STEP-RUN status
OFF : PAUSE disabled
PAUSE enable coil
ON : PAUSE enabled
SM206
OFF : Device test not yet
Device test request
acceptance status
ON : Device test executed
OFF : Ignored
SM210
Clock data set request
ON : Set request
OFF : No error
SM211
Clock data error
ON : Error
OFF : Ignored
SM212
Clock data display
ON : Display
Clock data read
OFF : Ignored
SM213
request
ON : Read request
OFF : Online module change
Online module change
SM235
flag
ON : Online module change
OFF :Online module change
Online module change
SM236
complete flag
ON : Online module change
OFF : No. 1 CPU reset
SM240
No. 1 CPU reset flag
ON : No. 1 CPU resetting
OFF : No. 2 CPU reset
SM241
No. 2 CPU reset flag
ON : No. 2 CPU resetting
OFF : No. 3 CPU reset
SM242
No. 3 CPU reset flag
ON : No. 3 CPU resetting
OFF : No. 4 CPU reset
SM243
No. 4 CPU reset flag
ON : No. 4 CPU resetting
OFF : No. 1 CPU normal
SM244
No. 1 CPU error flag
ON : No. 1 CPU during stop
OFF : No. 2 CPU normal
SM245
No. 2 CPU error flag
ON : No. 2 CPU during stop
OFF : No. 3 CPU normal
SM246
No. 3 CPU error flag
ON : No. 3 CPU during stop
*1: This applies to the CPU of function version B or later.
TableApp.3 Special relay
Meaning
• When this relay goes from OFF to ON, the LEDs
ON : LED OFF
corresponding to the individual bits at SD202 go off
• Goes ON at STOP status
• Goes ON at PAUSE status
• Goes ON at STEP-RUN status
• PAUSE status is entered if this relay is ON when the
PAUSE contact goes ON
• Comes ON when the device test mode is executed
executed
on GX Developer.
• When this relay goes from OFF to ON and after END
instruction execution of subsequent scan, clock data
stored in SD210 to SD213 are written to the CPU
module.
• ON when error is generated in clock data (SD210 to
SD213) value, and OFF if no error is detected.
• Displays clock data as month, day, hour, minute, and
second at the LED display at front of CPU
module.(Enabled only for Q3ACPU and Q4ACPU)
• When this relay is ON, clock data is read to SD210 to
SD213 as BCD values.
is not in progress
Turns on during online module change. (for host PLC)
in progress
• Turns ON for one scan after online module change is
incomplete
complete.
• This contact point can only be used by the scan
complete
program. (for host PLC)
• Goes OFF when reset of the No. 1 CPU is canceled.
• Comes ON when the No. 1 CPU is resetting
cancel
(including the case where the PLC is removed from
the base).
The other PLCs are also put in reset status.
• Goes OFF when reset of the No. 2 CPU is canceled.
• Comes ON when the No. 2 CPU is resetting
(including the case where the PLC is removed from
cancel
the base).
The other PLCs result in "MULTI CPU DOWN" (error
code: 7000).
• Goes OFF when reset of the No. 3 CPU is canceled.
• Comes ON when the No. 3 CPU is resetting
cancel
(including the case where the PLC is removed from
the base).The other PLCs result in "MULTI CPU
DOWN" (error code: 7000).
• Goes OFF when reset of the No. 4 CPU is canceled.
• Comes ON when the No. 4 CPU is resetting
cancel
(including the case where the PLC is removed from
the base).The other PLCs result in "MULTI CPU
DOWN" (error code: 7000).
• Goes OFF when the No. 1 CPU is normal (including
a continuation error).
• Comes ON when the No. 1 CPU is during a stop
error
error.
• Goes OFF when the No. 2 CPU is normal (including
a continuation error).
• Comes ON when the No. 2 CPU is during a stop
error
error.
• Goes OFF when the No. 3 CPU is normal (including
a continuation error).
• Comes ON when the No. 3 CPU is during a stop
error
error.
Set by
Explanation
(When Set)
S (Status change)
S (Status change)
S (Status change)
S (Request)
S (Request)
S (During online
module change)
S (When online
module change is
complete)
S (Status change)
Appendix 1 Special Relay List
Corres-
ponding
Corresponding CPU
ACPU
M9
QnA
Qn(H)
U
New
QnPH
QnPRH
M9042
M9041
QnA
Qn(H)
M9054
QnPH
QnPRH
U
M9040
New
Rem
U
M9025
M9026
Q3A
U
M9027
Q4A
Q4AR
U
M9028
Rem
New
QnPH
New
*1
Q00/Q01
*1
Qn(H)
QnPH
New
*1
Qn(H)
QnPH
*1
Q00/Q01
*1
Qn(H)
QnPH
App
9
10
11
- 4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents