SM1055
SM808
*: 1 minute clock indicates the name of the special relay (M9034) of the ACPU.
TableApp.11 Special relay
Name
Meaning
2n minute clock(1
ns
ns
*
minute clock)
ON
Always ON
OFF
ON
Always OFF
OFF
ON
ON for 1 scan only
1 scan
after RUN
OFF
RUN flag(After
ON
RUN, OFF for 1
1 scan
OFF
scan only)
OFF : PAUSE disabled
PAUSE enable coil
ON : PAUSE enabled
OFF : PAUSE not in effect
USE status contact
ON : PAUSE in effect
STOP status
OFF : STOP not in effect
contact
ON : STOP in effect
OFF : Sampling trace in
Sampling trace
progress
completed
ON : Sampling trace
completed
OFF
ON
STRA
Same as
execution
Sampling trace
STRAR
ON
OFF
as execution
Watchdog timer
OFF : Does not reset WDT
(WDT) reset
ON : Resets WDT
OFF : Trace not in progress
Sampling trace
ON : Trace in progress
OFF : Sampling trace
Sampling trace
suspended
preparations
ON : Sampling trace started
Selection of
OFF : Output until NULL
number of
code encountered
characters output
ON : 16 characters output
CHG instruction
OFF : Enabled
execution disable
ON : Disable
SEG instruction
OFF : 7SEG segment display
switch
ON : I/O partial refresh
OFF : STEP RUN not in
STEP RUN flag
effect
ON : STEP RUN in effect
Status latch
OFF : Not completed
completion flag
ON : Completed
Details
• Alternates between ON and OFF according to the
seconds specified at SD414. (Default: n = 30)
• Not turned on or off per scan but turned on and off even
during scan if corresponding time has elapsed.
• Starts with off when PLC power supply is turned on or
CPU module reset is performed..
• Used as dummy contacts of initialization and application
instruction in sequence program.
• SM1038 and SM1037 are turned on and off without regard
to position of key switch on CPU module front. SM1038
and SM1039 are under the same condition as RUN status
except when the key switch is at STOP position, and
turned off and on. Switched off if the key switch is in STOP
position. SM1038 is on for one scan only and SM1039 is
off for one scan only if the key switch is not in STOP
position.
• When RUN key switch is at PAUSE position or pause
contact has turned on and if SM204 is on, PAUSE mode is
set and SM206 is turned on.
• Switched on when the RUN key switch or RUN/STOP
switch is in STOP position.
• Turned on upon completion of sampling trace performed
the number of times preset by parameter after
instruction is executed.
STRAR
Reset when
instruction is executed.
• Turning on/off SM803 can execute
instruction.
(SM803 is forcibly turned on/off by a peripheral device.)
When switched from OFF to ON:
Same
When switched from ON to OFF:
The value stored in SD1044 is used as the condition for
the sampling trace.
At scanning, at time
Time (10 ms unit)
• The SM1015 relay is turned on to reset the WDT when the
ZCOM instruction and data communication request batch
processing are executed (used when the scan time
exceeds 200 ms).
• Switched on during sampling trace.
• Sampling trace is not executed unless SM801 is turned
ON.
Sampling trace is suspended when SM801 goes OFF.
• When SM701 is OFF, characters up to NULL (00H) code
are output.
• When SM701 is ON, ASCII codes of 16 characters are
output.
• Switched ON to disable the CHG instruction.
• Switched ON when program transfer is requested.
Automatically switched OFF when transfer is complete.
• When SM1052 is ON, the SEG instruction is executed as
an I/O partial refresh instruction.
When SM1052 is OFF, the SEG instruction is executed as
a 7-SEG display instruction.
• Switched on when the RUN key switch is in STEP RUN
position.
• Turned on when status latch is completed.
• Turned off by reset instruction.
Appendix 1 Special Relay List
Corresponding CPU
STRA
QnA
Qn(H)
QnPH
STRA
/
STRAR
STRA
instruction
STRAR
instruction
QnA
App
9
10
11
- 16