3
SEQUENCE PROGRAM CONFIGURATION AND
EXECUTION CONDITIONS
(4) Settings for execution of fixed scan execution type program
3
3.3 Settings for Creation and Execution of Multiple Sequence Programs
- 51
3.3.5 Fixed scan execution type program
(a) Program
Set the execution type to "Fixed scan" in the program setting of the PLC
parameter dialog box. When using multiple fixed scan execution type programs,
register them in the order of execution.
After setting the execution type to "Fixed scan", set the fixed scan interval and
unit.
They can be set within the following ranges.
• When the unit is ms : 0.5 to 999.5ms(0.5ms units)
• When the unit is s : 1 to 60s (1s units)
Diagram 3.48 Program