Making UPS Settings

These settings control how the VessRAID subsystem detects the UPS unit and
responds to data reported by the UPS unit.
To make UPS settings:
1.
Click the Subsystem
2.
Click the UPS
3.
Click the Settings tab in Management View.
4.
Perform the following actions as required:
Verify the Current UPS Communication method. See Note 1 below.
Choose a Detection Setting from the dropdown menu:
Choose an Action Mode from the dropdown menu:
Type values into the Threshold fields. See Note 2 below.
For UPS units with network cards, type IP address or DNS name in the
field provided. See Note 3 below.
5.
Click the Submit button to apply your settings.
Notes
1.
VessRAID supports multiple UPS units using network or serial connections,
but a combination of both methods.
icon in Tree View.
icon.
SNMP – USB connection.
Serial – USB connection.
Unknown – No connection.
Automatic – Default. If a UPS is detected when the subsystem
boots, the setting changes to Enable.
Enable – Monitors UPS. Settings changes, reports warnings, and
logs events.
Disable – Monitors UPS only.
ShutDown – Shuts down the subsystem when a Threshold value is
exceeded.
None – No additional action when Threshold value is exceeded.
Running Time Remaining Threshold – Actual time below this
value resets adaptive writeback cache to writethrough.
Warning Temperature Threshold – Actual temperature above this
value triggers a warning and logs an event.
Battery Charge Remaining Threshold – Reserve capacity below
this percentage triggers a warning and logs an event.