Configure
The USER LINES menu option lets you configure the auxiliary status lines
User Lines
The Auxiliary (Aux) lines are 2 open collector outputs that can be used to monitor
the status of the power supply. The auxiliary lines are referred to as AUX A and
AUX B. See "Making Connections for Remote Control" on page 107 for details.
Each user line also has a corresponding annunciator on the front panel display to
indicate when it is on. Aux lines can be set up to report the following status
conditions:
•
None
•
Unregul: Output Unregulated
•
OVP: Over-Voltage Condition
•
UV: Under-Voltage Condition
•
OC: Over-Current Condition
•
UC: Under-Current Condition
•
OP: Over-Power Condition
•
UP: Under-Power Condition
•
AC Off: Input power has failed or is out of range
•
OTP: Over-Temperature Condition
•
Hi Temp: High-Temperature Condition
•
SenseProt: Sense Protection Tripped
•
Fold Prot: Fold Protection Tripped
•
CC: Constant Current Mode
•
CV: Constant Voltage Mode
•
CP: Constant Power Mode
•
Out ON: Output On
•
Out OFF: Output Off
To access and work with the USER LINES menu option:
Step # Do This
1
2
3
4
5
1. You can also press MENU again to bring up the AUX LINES option.
Release 3.0
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
MENU
1
ENTER
or
to select which
line to configure.
ENTER
Power Supply Operation
You Will See
ERROR MSGS
USER LINES
Aux line A
Aux line B
Cfg None
Operation