Analog Programming Interface 0-10V Range; Remote Interface Calibration Procedure; Output Voltage; Output Current - Xantrex XDC 10-600 Operating Manual

6000 watt and 12000 watt series digital programmable dc power supply
Hide thumbs Also See for XDC 10-600:
Table of Contents

Advertisement

Analog
The 0-10V range of the analog programming interface must be calibrated separately.
Follow the procedure exactly as for calibrating the 0-5V range, using the
Programming
corresponding 10V menu options. All the analog signals will be scaled by a factor of
Interface
2.
0-10V Range

Remote Interface Calibration Procedure

Calibration can also be done via front panel. See "Front Panel Calibration
Procedure" on page 183.
Calibration of voltage programming and readback are combined in a single
procedure.
Output
1. Set the load to open circuit. Attach a DVM across the output terminals.
Voltage
2. Minimum calibration level
Set the output voltage to 10% by sending the command:
CAL:OUTP:VOLT:LEV MIN
3. Enter voltage data
Enter the voltage read from the external DVM.
CAL:OUTP:VOLT:DATA <voltage>
4. Maximum calibration level
Set the output voltage to 90% by sending the command:
CAL:OUTP:VOLT:LEV MAX
5. Enter voltage data
Enter the voltage read from the external DVM.
CAL:OUTP:VOLT:DATA <voltage>
6. Power supply calculates and stores calibration constants.
Output
1. Set the power supply and load operate at full output. You must ensure the power
Current
supply is operating in current mode during current calibration. Place a shunt on
the load line so that you can measure the current. Attach a DVM across the shunt
2. Minimum calibration level
Set the output current to 10% by sending the command:
CAL:OUTP:CURR:LEV MIN
Release 3.0
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Calibration
Remote Interface Calibration Procedure
187

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents