Remote Operation
SCPI Commands for Digital Interfaces
Clear
To clear a protection mechanism that has tripped:
Protection
OUTP:PROT:CLE
Event
This will clear all protection mechanisms and re-enable the output. If the condition
that caused the alarm still exists, the protection will be allowed to trip again.
View Power
The following 3 commands query the voltage, current, or power being supplied at
the output terminals.
Supply
Output
To measure the voltage output:
MEAS:VOLT?
To measure the current output:
MEAS:CURR?
To measure the power output:
MEAS:POW?
Configure
To set up Auxiliary line A:
Auxiliary
OUTP:AUXA:SOUR <aux-line-mnemonic>
Status Lines
The choices for <aux-line-mnemonic> include:
•
NONE
•
ON: Output On
•
OFF: Output Off
•
OVOL: Over-Voltage Condition
•
UVOL: Under-Voltage Condition
•
OCUR: Over-Current Condition
•
UCUR: Under-Current Condition
•
OPOW: Over-Power Condition
•
UPOW: Under-Power Condition
•
ACOF: AC Power had been turned off or failed
•
OTEM: Over-Temperature Condition
•
HTEM: High-Temperature Condition
•
SPR: Sense Protection Tripped
•
FOLD: Fold Protection Tripped
•
CC: Constant Current Mode
•
CV: Constant Voltage Mode
•
CP: Constant Power Mode
•
UNR: Output Unregulated
134
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Operating Manual for XDC Series Power Supply