Output Hold-Up Time – Source Interruption
Minimum 4 ms with output deviation less than 5% of maximum output voltage after
source interruption.
Transient Response Time
Time to recover within 0.75% of rated output of previous level after step change in
load current between 50% and 100%.
Mode
Voltage Mode
Voltage Mode
Mode Crossover
Maximum deviation as a percentage of rated output voltage.
CV – CC Overshoot
Peak–Peak and RMS Noise Bandwidth Limits
The frequency range for Peak to Peak measurements is 10 Hz–20 MHz.
The frequency range for RMS measurements is 10 Hz–100 kHz.
Maximum Remote Sense Line Drop Compensation
Minimum 3.8 V for each line, 5 V typical
Isolation
AC Input to Output
AC Input to Chassis
Output to Chassis
1.
Time for the output voltage to recover within 0.75% of rated output of its previous level
after a step change in load current of up to 50% - 100% and 100% to 50% of rated
output
Release 3.0
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
1
Time
3 ms (6000 W models)
35 ms (12000 W models)
1%
1350 V
ac
1350 V
ac
600 V
ac
Specifications and Characteristics
Output Performance Specifications