Installation
Load Connection
Load
As a minimum, load wiring must have a current capacity greater than the output
Conductor
current rating of the power supply. This ensures that the wiring will not be damaged
even if the load is shorted.
Ratings
450 A/cm
maximum current rating results in an approximately 30 °C temperature rise for a
wire operating in free air. Where load wiring must operate in areas with elevated
ambient temperatures or bundled with other wiring, use larger gauges or wiring rated
for higher temperatures.
Table 2.3 Current Carrying Capacity for Load Wiring
Wire Size
(AWG)
20
18
16
14
12
10
8
Load Wiring
For applications using remote sensing, the voltage drop across each load line must
Length for
be limited to 1V or less.
may be used for a given load current and wire size to ensure that this limit is not
Operation
exceeded.
with Sense
Lines
Figure 2.4 Maximum Load Wire Length
38
Table 2.3
2
, for various gauges of wire rated for 105 °C operation. Operating at the
Maximum Current (A)
2.5
4
6
10
16
21
36
Figure
shows the maximum current rating, based on
Wire Size
Maximum Current (A)
(AWG)
6
61
4
97
2
155
1
192
1/0
247
2/0
303
2.4, shows the maximum allowable wire length that
Operating Manual for XKW 3kW Series Power Supply