Installation
Local and Remote Sensing
4. To prevent ground loops, ground the sense line shield, at one point only, to the
5. Turn the power supply ON.
Notes:
1. If you operate the power supply with remote sense lines connected to the load
2. If you operate the power supply without remote sense lines or local sense
Figure 2.12 shows a sample setup for using remote sensing.
Figure 2.12Connecting Remote Sense Lines
56
power supply's return output connection at the load, to the power supply's return
output at its negative output terminal, or to the power supply's chassis.
and with either of the positive or negative load lines not connected, the power
supply shutdown circuit will activate, causing the output voltage and current to
fall to zero.
jumpers in place, the supply will continue to work, but supply regulation will be
degraded and/or erratic, or, the OVP circuit may activate.
Operating Manual for XFR 2.8kW Series Power Supply