Setup Current Sharing Network - Xantrex XDC 10-600 Operating Manual

6000 watt and 12000 watt series digital programmable dc power supply
Hide thumbs Also See for XDC 10-600:
Table of Contents

Advertisement

SCPI
Select whether the unit will operate as a master or slave unit:
SOURCE:COMBine:CSHare:MODE [MASTer | SLAVe | OFF]
To query the total output current of all current sharing units, use the SCPI command:
MEAS:CURR? SUM
The current share subregister (CSHare) will show whether the master or slave is
operating.
STAT:OPER:CSH:COND?
See Table 4.14, "Current SHare Sub-Register," on page 148 for a description of the
bits in this register.
Setup
To set up multiple supplies for current share operation, follow these steps:
Current
1. Configure each supply with a unique multichannel address. (See "Multichannel
Sharing
Operation (6000 Watt only)" on page 113.)
Network
Configure one supply to operate as the master. Configure others to operate as
slaves.
2. Power down the units. Connect the CAN ports of all paralleled units as you
would for multichannel operation
3. Make load connections. It is recommended to keep load cables the same length
if possible. See Figure 5.1.
4. Power up the master, then all slaves.
5. Set the voltage on the master, then enable the output.
Release 3.0
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Current Sharing (6000 Watt only)
Overview
175

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents