Maintenance Object Repair Procedure
Table 8-506. Test #40 Tone Generator Transmission Test
Error
Test
Code
Result
Description / Recommendation
None
ABORT
The system was not able to allocate all the resources needed for this test or
there was an Internal system error.
1
ABORT
The system could not allocate all the resources needed to test the DTMF
tones.
1001
ABORT
The system was not able to put the tone generation facility in the appropriate
mode to test it.
1002
ABORT
The system could not allocate time slots for the test connection. This can
happen when the system is heavily loaded. If the system is not heavily
loaded, then test the TDM bus via the test tdm port-network PN# command.
1. Retry the command at 1-minute intervals up to 5 times.
1003
ABORT
The system could not allocate a tone receiver for the test connection. This
can happen when the system is heavily loaded or there is not a Tone Detector
circuit pack in the port network where this test is being executed.
1. Make sure there is a Tone Detector circuit pack in the same port network.
2. If a Tone Detector circuit pack is missing, install one in the same port
3. Allow approximately 1-minute for Tone Detector maintenance to run on
4. Retry the command at 1-minute intervals up to 5 times.
1022
ABORT
[G3r V2] Tone detection for the system is administered as wide broadband
(tone detection mode 5), and the Tone Detector used for this test was not a
TN420C. (the only circuit packs with this capability). GPTD ports on other
types of Tone Detector circuit packs are taken out of service since they cannot
provide the administered function. Either:
2000
ABORT
Response to the test request was not received within the allowable time
period. System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2100
ABORT
System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
1 (a)
FAIL
DTMF generation failed for the active tone generator.
105 (a)
FAIL
Generation of 440-Hz failed.
109 (a)
FAIL
Generation of 2225-Hz failed.
110 (b)
FAIL
Generation of 404-Hz level invalid.
8-1192
Issue 1 May 2002
network.
the newly inserted Tone Detector circuit pack.
Change the tone-detection mode administered on the system-parameters
country-options form (refer to DEFINITY Communications System
Generic 3 V2 Implementation, 555-230-653).
Remove all non-TN420C circuit packs from the system.
Continued on next page
555-233-142