Avaya S8700 Maintenance Manual page 142

Avaya s8700 media server for ip connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Maintenance Object Repair Procedure
Table 8-357. Test #9 NPE Cross Talk Test
Error
Test
Code
Result
Description / Recommendation
1000
ABORT
System resources required to run this test are not available. The port may be
in use on a valid ISDN-PRI test call. Use the list isdn-testcall command to
determine whether the port is in use (listed in the M/T Port column). If so,
either wait for the test call to finish (as indicated in the
Duration
isdn-testcall grp/mem command, where grp/mem is determined from the
B-channel
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to abort and the port is idle, escalate the problem.
1001
ABORT
System resources required to run this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to abort, escalate the problem.
1002
ABORT
The system could not allocate time slots for the test. The system may be under
heavy traffic conditions or it may have time slots out of service due to
TDM-BUS errors.
1. If the system has no TDM-BUS errors and is not handling heavy traffic,
2. If the test continues to abort, escalate the problem.
1003
ABORT
The system could not allocate a tone receiver for the test. The system may be
oversized for the number of tone detectors present or some tone detectors may
be out-of-service.
1. Resolve any TTR-LEV errors.
2. Resolve any TONE-PT errors.
3. If neither condition exists, retry the test at 1-minute intervals up to 5 times.
4. If the test continues to abort, escalate the problem.
1004
ABORT
The port has been seized by a valid ISDN-PRI test call. Use the list
isdn-testcall command to determine which call is using the port (from the
M/T Port column). Either wait for the test call to complete (as indicated in the
Start Time
call with the clear isdn-testcall grp/mem command, where grp/mem is
determined form the
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to abort and the port is idle, escalate the problem.
8-838
Issue 1 May 2002
fields in the above display), or abort the test call with the clear
field of the above display.
repeat test at 1-minute intervals up to 5 times.
and
Duration
B-channel
Start Time
fields of the above display), or abort the test
field of the above display.
Continued on next page
and
555-233-142