4.2.7.
4.2.7. Setting Current Limit Level
Setting Current Limit Level
From the HOME screen, press EDIT/ENTER six (6) times, until the Edit Current Limit Level
Screen is visible, 'Current Limit A)', on top of display. To set this parameter follow the steps in
Section
4.2.1.
After setting the Current Limit level to the desired value and pressing EDIT/ENTER to save the
set point, configuration of Basic ATevo Set Points and Alarms is complete and the display
returns to the HOME screen.